Parsec Data Center
Parsec Data Center Data Center, USA
FACILITY SPECIFICATIONS
Data center leasable/co-location space consists
of 4 separate suites
· Suite #1: 2098 sq feet
· Suite #2: 2385 sq feet
· Suite #3: 2233 sq feet
· Suite #4: 2385 sq feet
Floor load: 250 lbs per square foot
Roughly 11 feet between the raised floors and
the ceiling
24 inch raised flooring
Ground ring protection against lightning and
power surges
Exterior blast proof walls
ELECTRICAL POWER SYSTEMS
COST
· Approximately .09/kWH
COMMERCIAL POWER
· Runs off commercial power, backed up by a
standby generator, 120 or 208 volt with two
20 or 30 amp circuits
BATTERY BACKUP
· A redundant battery backup provides 120 or
208 volt with two 20 or 30 amp circuits
STANDBY GENERATOR
· 1,000 Gallon 800 KW Diesel Generator, with a
24 hour run time
NETWORK CONNECTIVITY
Multiple active Internet connections
Redundant diverse fiber paths
Additional bandwidth is available with built-in
scalability
ENVIRONMENTAL CONTROLS
FIRE SUPPRESSION
· Fire suppression system utilizing Fike's
Ecaro-25
· Ecaro-25 features fire-extinguishing agent
FE-25 by DuPont. FE-25 absorbs heat energy
at its molecular level faster than the heat can
be generated, so the fire cannot sustain
itself.
· FE-25 also forms free radicals to chemically
interfere with the chain reaction of the
combustion process. This highly effective
clean agent is safe for people, assets and the
environment. FE-25 is:
- Zero Ozone Depleting Potential (ODP)
- Environmentally Safe
- Electrically Non-Conductive
- Colorless and Odorless
- Leaves No Residue
- No Over pressurization Concerns
HVAC
· N+1 Liebert Drycoolers 60 Hz
· N+1 Liebert Chillers
· N+1 Glycol Pumps
TEMPERATURE
· 65 - 72 degrees F, monitored to stay within
that range 24x7x365
HUMIDITY
· 35 - 50 %, monitored to stay within that
range 24x7x365
SECURITY SYSTEMS
Two Factor, key pad and RFID card exterior
authentication
Man Trap
Biometric Iris Scanning authentication access
to interior data center and data center suites
Locked cages and server cabinets
Exterior and interior video surveillance
Access controlled meet me/electrical room
Access controlled glycol pump house
SYSTEM MONITORING
On site monitoring systems provide real time
information on all critical support systems
Temperature, humidity and power are
monitored 24x7x365
Fire and water detectors are also in place and
monitored 24x7x365
Parsec Data Management,
Montana,
USA
3450 Gabel Road, 59102 Billings, Montana
59102